Water Sump & Water Tank Capacity Calculator

Calculate underground water sump and overhead water tank capacity in Litres, Gallons, Cubic Feet, and Tanker loads. Supports simultaneous Feet-Inches and Metric Meter measurements.

Tank Dimensions (Inner Water Volume)

Feet & Inches
10 ft 0 in (3.05 m)
ft
in
8 ft 0 in (2.44 m)
ft
in
6 ft 0 in (1.83 m)
ft
in
Usually 9 in (225 mm)
inches
Total Effective Water Capacity
13,592 Litres
≈ 2.3 Commercial Tankers (6,000L loads)
US Gallons: 3,591 gal Cubic Feet: 480 ft³ Cubic Meters: 13.59 m³
Cross-Section Water Level Total Depth: 6' 9"
Freeboard Air Clearance: 9"
Water Level: 6' 0" (13,592 L)
Family Coverage
20 Days
For a 5-member family at 135 LPCD
Excavation Volume
684 ft³
Outer pit including 6" RCC walls

Complete Engineering Guide: Underground Water Sump & Water Tank Sizing

An Underground Water Sump is a subterranean reservoir constructed from reinforced cement concrete (RCC) or brick masonry to store water from municipal piped supplies (such as Cauvery, Jal Board, BWSSB, or DJB) or borewells. Because water supply in most Indian urban agglomerations is intermittent, an accurately sized sump is mandatory to ensure uninterrupted domestic pressure and hygiene.

1. National Building Code (NBC) Water Consumption Norms

Under the Bureau of Indian Standards code IS 1172:1993, domestic water requirements per capita are standardized as follows:

2. Sizing Formula: Water Sump vs. Overhead Tank (OHT)

A sound civil engineering rule of thumb dictates that the underground sump capacity should equal 1.5 to 2.0 times the daily domestic demand, while the overhead roof tank (OHT) should equal approximately 0.5 times (half day) to 1 day of demand. This distribution ensures the rooftop structure does not endure excessive static dead load while the underground sump buffers against 2 to 3 days of supply failure.

Capacity (Litres) = Length (ft) × Width (ft) × Water Depth (ft) × 28.3168

3. Why Freeboard Clearance is Critical

Never fill a sump up to the top structural slab. A mandatory freeboard clearance of 225 mm to 300 mm (9 to 12 inches) must be maintained between the maximum high-water level and the bottom of the roof slab. Freeboard provides:

4. RCC vs. Brick Masonry: Which is Best for Sumps?